800-353-9425

Non-Penetrating Rooftop Access Platform with Integrated Davit Crane

Safely hoist mechanical equipment over elevated roof parapets without piercing your roof envelope, voiding manufacturer warranties, or introducing hot-work hazards.

Talk to an ExpertTalk to an Expert

Or, give us a call: 1-800-353-9425

Non-Penetrating Rooftop Hoist Platforms

Manually hauling mechanical equipment over rooftop parapet walls exposes maintenance teams to severe fall hazards and costs facilities thousands in unnecessary mobile crane and boom lift rentals. Flexible Lifeline Systems’ engineered counterweighted rooftop platform with davit crane delivers a permanent material handling station designed specifically for routine service loads up to 550 lbs. Built as a completely freestanding system, this non-penetrating rooftop hoist platform passively secures the work area without drilling anchor bolts, welding to building steel, or voiding valuable roofing membrane warranties.

Functioning as a stand alone parapet material handling platform, the system pairs an elevated Kee Step℠ access platform with an integrated davit arm to safely clear exterior parapets up to 4 feet 10 inches tall. Maintenance personnel operate the manual or electric hoist while fully enclosed behind OSHA-compliant guardrails, eliminating the need for active harness tie-offs. To ensure structural integrity, high-density recycled PVC counterweight bases are engineered to span and align directly over the building’s structural bar joists, dissipating heavy point loads into the primary framework. Fully compliant with OSHA 1910.29, OSHA 1926.502, and AISC standards, FLS provides certified turnkey installations with zero hot work and zero roof penetrations.

Single-Source Fall Protection and Material Handling

FLS Fall Protection Specialists engineer, deliver, and certify purpose-built rooftop platforms of all types, including this one, to solve your site's specific access and maintenance challenges. Contact a Fall Protection Specialist today to eliminate crane rentals and protect your building envelope.

What are safe methods to access roofs?

Fixed ladder, temporary ladders, stairs and manlifts are all potentially safe methods of accessing a roof.  A job hazard analysis should be performed to ensure the access can be done in a safe manner.  If near the edge, protecting access points with additional guardrail around the access point to protect the worker once on the roof should also be considered.  Depending on the height of a fixed ladder it may require additional fall protection. Ensure temporary ladders are used correctly and extend above the roof level and are not near a roof corner.  When using a man lift to access a roof ensure it can extend to a safe place to access the roof before exiting.

Do you need fall protection on a ladder?

For permanent ladders as of 2017 OSHA updated standard requirements for fall protection on a ladder, to no longer allow cages as means of fall protection. All fixed ladders more 24ft in height require fall protection. Existing cages must be removed by 2036. Examples of fall protection for ladders include Vertical Lifelines and Ladder Davit Systems.  If a cage remains on the ladder it must not interfere with the performance of the fall protection system.

Regulatory Codes & Standards

Industrial rooftop material handling requires strict alignment between general safety mandates and rigorous structural design. Integrating an elevated access platform with a lifting davit creates overlapping regulatory challenges: maintaining fall containment for technicians operating at the roof perimeter while safely managing dynamic and static load transfer into the host building without penetrating the roof envelope.

The system directly satisfies each applicable standard through specific engineering controls:

  • OSHA 1910.29 (Fall Protection Systems and Falling Object Protection Criteria and Practices):

    • Code Requirement: Regulates general industry walking-working surfaces, specifying that guardrail top rails must stand at 42 inches (plus or minus 3 inches) above the walking surface, resist a minimum concentrated force of 200 pounds applied in any outward or downward direction, and provide compliant midrails, toeboards, and stair rails.

    • Product Implementation: The elevated KeeStep bridge and access stairs incorporate standard 42-inch top rails and midrails constructed from Schedule 40 galvanized steel pipe using slip-on Kee Klamp fittings. This assembly forms an OSHA-compliant physical safety barrier that encloses technicians during hoist operations, eliminating edge-fall exposure and the need for active harness tie-offs.

  • OSHA 1926.502 (Fall Protection Systems Criteria and Practices):

    • Code Requirement: Outlines structural performance requirements for construction and multi-trade working surfaces, mandating structural safety factors, deflection limits under 200-pound edge loads, and structural platform integrity under live working conditions.

    • Product Implementation: The working bridge surface is engineered to support a continuous 30 psf live working load. Structural uprights and platform frames use high-yield ASTM steel tubing and bolted mechanical connections designed to prevent structural failure or excessive deflection during rigorous maintenance and staging tasks.

  • AISC 15th Edition Steel Construction Manual:

    • Code Requirement: Serves as the premier national design standard governing structural steel design, member capacity sizing, connection detailing, and allowable stress or load and resistance factor design (LRFD).

    • Product Implementation: All structural rolled shapes, plates, and tubing comply with ASTM A572 Grade 50 and ASTM A500 Grade B specifications. High-strength bolted connections utilize ASTM A325 Type 1 structural hardware installed to snug-tight criteria. Crucially, the entire modular structure is engineered with zero field welds, avoiding on-site steel compromise, inspection delays, and structural fatigue.

  • Third-Party / Engineering Certification (PE Stamped Calculations):

    • Code Requirement: Verifies that dynamic lifting moments, live personnel weights, and total system dead loads do not exceed the capacity of the host building’s structural frame.

    • Product Implementation: Every installation includes site-specific calculation packages reviewed and wet-stamped by a licensed Professional Engineer (PE). To prevent localized deck crushing without piercing the weatherproofing membrane, the system uses custom-spaced, non-penetrating PVC counterweight bases that position point loads directly over the building’s underlying bar joists and primary steel framing.

      X